The compact driver performs control and monitoring of a circuit breaker within a complex control and protection device managed by MPU-5 series control modules. It is designed to receive commands and reports status via frontal user-accessible binary inputs and outputs, as well as internal CAN bus to cooperate with other modules within the assembly.
Parameter | DRVU-4 |
---|---|
Auxiliary supply voltage, V | 85-265 AC |
Number of command inputs | 2 x volt free type |
Number of status outputs | 3 x changeover relay type |
Configuration port | NA |
Close pulse voltage, V | 380 |
Close pulse energy, J | not less than 120 |
Trip pulse voltage, V | 380 |
Trip pulse energy, J | not less than 8 |
Circuit breaker position detection | Actuator control pulse |
Internal controller interface | CAN + power |